VAMP Ltd
Overcurrent and earth-fault relay
Technical Description
VAMP 130
VM130.EN003
Vamp 24h support phone : +358 (0)40 573 6316
33
Potential-free contacts for position indication must be available
in the protected application.
4.2.
Auxiliary voltage
The external auxiliary voltage Uaux (standard 40 to 265 V ac/dc
or 24 V dc, option B) for the relay is connected to the terminals
X1: 11 - 12
Note!
Polarity of the auxiliary voltage U
aux
(24 V dc, option B):
+ = X1:11 and - = X1:12.
4.3.
Output relays
The VAMP 130 relay is equipped with five configurable output
relays and a separate output relay for the self-supervision
system
x
Trip relays T1 and T2 (terminals X2: 19 - 20 and 16 - 17)
x
Alarm relays A1 - A3 (terminals X2: 13 - 14, 11 - 12 and 9 -
10)
x
Self-supervision system output relay IF (terminals X2: 7 - 8)
x
The trip relay T2 can also be used for alarm purposes.
4.4.
Serial communication connection
RS 232 serial communication connection for computers,
connector LOCAL (RS 232) on the front panel of the relay