Generator protection relay
Technical description
VAMP 210
VM210.EN004
Vamp 24h support phone: +358 (0)20 753 3264
49
5.2.
Tests and environmental conditions
5.2.1.
Disturbance tests (EN 50263)
Emission
- Conducted (EN 55022)
0.15 - 30 MHz
- Emitted (EN 55022)
30 - 1 000 MHz
Immunity
- Static discharge (ESD)
EN 61000-4-2, class III
6 kV contact discharge
8 kV air discharge
- Fast transients (EFT)
EN 61000-4-4, class III
2 kV, 5/50 ns, 5 kHz, +/-
- Surge
EN 61000-4-5, class III
1 kV, 1.2/50
µ
s, common mode
2 kV, 1.2/50
µ
s, differential mode
- Conducted RF field
EN 61000-4-6
0.15 - 80 MHz, 10 V/m, 80% AM (1 kHz)
- Emitted RF field
EN 61000-4-3
80 - 1000 MHz, 10 V/m, 80% AM (1 kHz)
- GSM test
EN 61000-4-3
900 MHz, 10 V/m, pulse modulated
1 MHz burst
IEC 60255-22-1
1 kV, differential mode
2,5 kV, common mode
Voltage interruption
IEC 60255-11
5.2.2.
Test voltages
Insulation test voltage
(IEC 60255-5)
2 kV, 50 Hz, 1 min
Surge voltage (IEC 60255-5)
5 kV, 1.2/50
µ
s, 0.5 J
5.2.3.
Mechanical tests
Vibration (IEC 60255-21-1)
10...60 Hz, amplitude ±0.035 mm
60...150 Hz, acceleration 0.5g
sweep rate 1 octave/min
20 periods in X-, Y- and Z axis direction
Shock (IEC 60255-21-1)
half sine, acceleration 5 g, duration 11 ms
3 shocks in X-, Y- and Z axis direction
5.2.4.
Environmental conditions
Operating temperature
0 to +55
°
C
Transport and storage temperature
-40 to +70
°
C
Relative humidity
< 75% (1 year, average value)
< 90% (30 days per year, no condensation
permitted)