Parameters of the underfrequency protection:
f<, f<< (81)
Parameter: Value/unit:
Measured
value
f Hz
Frequency
f<, f<<
Hz
Frequency as primary value
t<, t<<
s
Operating time
Setting
values
Ublock %Ugn
Setting of the undervoltage
blocking in % of Ugn
SCntr
Cumulative
start
counter
TCntr
Cumulative trip counter
Flt %
Min. frequency under a fault
situation
Recorded
values
EDly %
Elapsed time as compared to the
set operating time, 100% =
tripping
2.2.14.
Circuit-breaker failure protection (50BF)
The operation of the circuit-breaker failure protection is based
on the supervision of the operating time, from the pick-up of
the configured trip relay to the dropout of the same relay. If
that time is longer than the operating time of the CBFP stage,
the CBFP stage activates another output relay, which will
remain activated, until the primary trip relay resets.
The CBFP stage operates overcurrent and earth fault
situations, because its function is merely based on supervision
of the control of the output relay.
Parameters of the circuit-breaker failure protection:
CBFP (50BF)
Parameter: Value/unit:
CBRel
Output relay to be supervised
Setting
values
t> s
Operating
time
SCntr
Cumulative start counter, only
selected ArcCn arc activations
TCntr
Cumulative trip counter
Recorded
values
EDly %
Elapsed time as compared to the
set operating time, 100%=tripping