VAMP Ltd
Generator protection relay
Technical description
VAMP 210
VM210.EN004
Vamp 24h support phone: +358 (0)20 753 3264
35
Optional accessories are available for RS 485 connection (VMA
3 CG), Ethernet connection over TCP/IP protocol (VEA 3 CG)
and ProfiBus connection (VPA 3CG). Please see the
corresponding documentation for more details.
Option modules
Standards
interface
Internal
Internal Internal External
Protocol
RS 232:
VX004-M3
or VX008-
4
Plastic
or Glass
RS 485:
ProfiBus:
Ethernet:
VX003 +
(VX004-
M3)
ModBus
X X X
SPA-Bus
X X X
ProfiBus
X
IEC-60870-5-
103
X X X
ModBus/
TCP
X
Transparent
TCP/IP
X
2.6.
Disturbance recorder
The disturbance recorder can be used to record all measured
signals i.e. currents and voltages, status information of digital
inputs (DI) and digital outputs (DO). The digital inputs include
also the Arc light information. The digital outputs include the
Arc binary output information (BO).
Recorder capacity is 48 000 bytes. There can be a maximum of
5 recordings and the maximum selection of channels in one
recording is 12 (limited in waveform recording).
The recorder can be triggered by any protection stage start or
trip signal. The trig signal is selected in the output matrix. The
recording can also be triggered manually.
When recording is made also the time stamp will be
memorized.
The recordings can be viewed by VAMPSET program. The
recording is in COMTRADE format so also other programs can
be used to view the recordings.
For more detailed information, see separate Disturbance
Recorder manual VMDR.EN0xx.