VAMP Ltd
Generator protection relay
Operation and configuration
VAMP 210
VM210.EN004
Vamp 24h support phone: +358 (0)20 753 3264
31
Figure 7.1.1-1 Principle for scaling the measured values of the VAMP 210
relay.
7.
Activation of desired protection functions, Prot menu. See
chapter 5.5 on page 25.
8.
Setting values of the protection function parameters (e.g. I>
menu). See the technical description chapter 2 onward for
appropriate protection function.
9.
Routing of trip and alarm signals from the protection
functions to the desired output relays and LED indicators
(DO menu). See chapter 5.4 on page 25.
10.
Configuration of blocking matrix (Prot menu). See chapter
5.5 on page 25.
11.
Configuration of desired DI inputs, e.g., external blockings
(DI menu), see chapter 5.3 on page 25.
12.
Configuration of communication parameters (Bus menu),
see chapter 5.8 on page 28.
7.1.2.
Configuration example
The example below illustrates the calculation and scaling of
setting values and the grouping of output relays in a typical
protection configuration. The values given in the example are
to be regarded as guidelines only.
Example: Generator connected directly to busbar
The application uses the following protection functions and
parameters:
•
Definite time overcurrent protection (I>, k, Type)
•
Two-stage overvoltage protection (U>, t>; U>>, t>>)
•
Undervoltage protection (U<, t<, NoCmp, I<Blk)
•
Reverse power (P<, t<)
•
Unbalanced load protection (K1, I2, Type)
•
Underexcitation protection (Q@P0%, Q@P80%, t)
•
Underfrequency protection (f<, t<, Ublock)
•
Overfrequency protection (f>, t>)