VAMP Ltd
Generator protection relay
Operation and configuration
VAMP 210
VM210.EN004
Vamp 24h support phone: +358 (0)20 753 3264
23
5.
Configuration and parameter
setting
Operating level: CONFIGURATION
•
Choose and configure the digital inputs in the DI position of
the main menu.
•
Configure the digital outputs in the DO position of the main
menu.
•
Choose and configure the protection functions and configure
the interlockings in the Prot position of the main menu.
•
Change the parameters of the protection functions in the
function-related submenus, e.g. I>.
•
Set the ”Device Setup”, the scaling (e.g. of Inom, Isec, etc.),
date and time in the CONF position of the main menu.
•
Choose and configure the communication buses in the Bus
position of the main menu.
NOTE!
Some of the parameters can only be altered via the RS-232
serial port using a PC, e.g. changing password.
5.1.
Principle of parameter setting
1.
Move to the setting state of the desired menu, e.g.
CONF/CURRENT SCALING, by pushing the ENTER key.
The Pick text appears in the upper left part of the display.
2.
Supply the password associated with the configuration level
(default value = 0002).
3.
Scroll through the parameters with the UP and DOWN
keys. If a certain parameter can be set, the cursor to the left
of the value takes the form of a black filled triangle. If the
parameter cannot be set the cursor takes the form of a non-
filled triangle.
4.
Select the desired parameter, e.g. Inom, with the ENTER
key.
5.
Use the UP and DOWN keys to change a parameter value.
If the value contains more than one digit, use the LEFT and
RIGHT keys to step from digit to digit, and the UP and
DOWN keys to change the digits.
6.
Push the ENTER key to accept the new value.
7.
If you want to leave the parameter value unchanged, then
exit the edit state by pushing the CANCEL key.