VAMP Ltd
Generator protection relay
Operation and configuration
VAMP 210
VM210.EN004
Vamp 24h support phone: +358 (0)20 753 3264
25
•
f
•
Uo, UL3, UL2, UL1
•
U31, U23, U12
•
Io2, Io
•
IL3, IL2, IL1
5.3.
Configuring digital inputs DI
Via the submenus of the digital inputs menu the following
functions can be read and set:
•
Status of digital inputs (DIGITAL INPUTS)
•
Operation delay (DELAYs for DigIn)
•
Polarity of the input signal (INPUT POLARITY), either
normally open (NO) or normally closed (NC) circuit
•
Selection to event register EVENT MASK1 and EVENT
MASK2
5.4.
Configuring digital outputs DO
Via the submenus of the digital outputs menu the following
functions can be read and set:
•
Status of the output relays (RELAY OUTPUTS1 and 2)
•
Forcing of the output relays (RELAY OUTPUTS1 and 2)
(only if Force = ON):
o
Forced control (0 or 1) of the Trip relays T1 and T2
o
Forced control (0 or 1) of the Alarm relays A1…A5
o
Forced control (0 or 1) of the IF relay
•
Configuration of the output signals to the output relays T1
and T2, A1 - A5 and the operation indicators (LED) Alarm
and Trip, that is, the output relay matrix.
5.5.
Configuring protection functions Prot
Via the submenus of the Prot menu the following functions can
be read and set:
•
In the Prot menu you can reset all counters (PROTECTION
SET/ClALL)
•
Read the status of all protection functions (PROTECT
STATUS 1-3)
•
Enable and disable protection functions (ENABLED
STAGES 1-3)
•
Define the interlockings between signals.