MCP-8I Quick Start Guide
How to Configure the CGS Sensor for a Continuous Gluing Application
The ‘
Encoders Z-Pulse
’ will be used to trigger the CGS Sensor’s Inspection Evaluation Process.
The Sensor Channel’s ‘
Scanner
’ parameter will need to be set to ‘
Z-Signal Encoder
’.
The Sensor Channel’s ‘
Distance to Scanner
’ parameter should be set to 0 mm.
The Sensor Channel’s ‘
Reference Mode
’ parameter should to be set to ‘
Manual
’.
The Sensor Channel’s ‘
Glue Correction – Start / End
’ parameters should be set to 0 mm.
Each of these parameters are found under the ‘
Inspection Channel’s Settings Menu
’.
Here are instructions to navigate to the settings menu:
1. Navigate to the
‘Inspection Window’
by pressing the button labeled ‘
INSPECT
’.
Figure 112: Navigating to the Inspection Window
2. Navigate to the ‘
Inspection Channel’s Settings Menu
’ by pressing the ‘
Wrench
’ button.
Figure 113: Navigating to the Sensor Channel's Settings
3. Find and set each of the parameters mentioned above in the parameter list.