VDF650
User
Manual
Desc
ription
of
Function
Codes
-
239
-
Group
AC
:
AI
/
AO
Correction
Function
Code
Parameter
Name
Setting
Range
Default
AC
-
00
AI1
measured
voltage
1
0
.
500
–
4
.
000
V
Factory
-
corrected
AC
-
01
AI1
displayed
voltage
1
0
.
500
–
4
.
000
V
Factory
-
corrected
AC
-
02
AI1
measured
voltage
2
6
.
000
–
9
.
999
V
Factory
-
corrected
AC
-
03
AI1
displayed
voltage
2
6
.
000
–
9
.
999
V
Factory
-
corrected
AC
-
04
AI2
measured
voltage
1
0
.
500
–
4
.
000
V
Factory
-
corrected
AC
-
05
AI2
displayed
voltage
1
0
.
500
–
4
.
000
V
Factory
-
corrected
AC
-
06
AI2
measured
voltage
2
6
.
000
–
9
.
999
V
Factory
-
corrected
AC
-
07
AI2
displayed
voltage
2
9
.
999
–
10
.
000
V
Factory
-
corrected
AC
-
08
AI3
measured
voltage
1
9
.
999
–
10
.
000
V
Factory
-
corrected
AC
-
09
AI3
displayed
voltage
1
9
.
999
–
10
.
000
V
Factory
-
corrected
AC
-
10
AI3
measured
voltage
2
9
.
999
–
10
.
000
V
Factory
-
corrected
AC
-
11
AI3
displayed
voltage
2
9
.
999
–
10
.
000
V
Factory
-
corrected
These
parameters
are
used
to
correct
the
AI
to
eliminate the
impact
of
AI
zero
offset
and
gain
.
They have been corrected upon delivery
.
When you resume the factory values
,
these
parameters
will
be
restored
to
the
factory
-
corrected
values
.
Generally
,
you
need
not
perform
correction
in
the
applications
.
Measured
voltage
indicates
the
actual
output
voltage
value
measured
by
instruments
such
as
the
multimeter
.
Displayed
voltage
indicates
the
voltage
display
value
sampled
by
the
AC
drive
.
For
details
,
refer
to
U0
-
21
,
U0
-
22
and
U0
-
23
.
During correction
,
send two voltage values to each AI terminal
,
and save the measured
values
and
displayed
values
to
the
function
codes
AC
-
00
to
AC
-
11
.
Then
the
AC
drive
will
automatically
perform
AI
zero
offset
and
gain
correction
.
If
the
input
voltage
and
the
actual
voltage
sampled
by
the
AC
drive
are
inconsistent
,
perform
correction
on
site
.
Take
AI1
as
an
example
.
The
on
-
site
correction
is
as
follows
:
1
)
Send
a
voltage
signal
(
approximately
2
V
)
to
AI1
.
2
)
Measure
the
AI1
voltage
and
save
it
to
AC
-
00
.
3
)
View
the
displayed
value
of
U0
-
21
and
save
the
value
to
AC
-
01
.
4
)
Send
a
voltage
signal
(
approximately
8
V
)
to
AI1
.
5
)
Measure
AI1
voltage
and
save
it
to
AC
-
02
.
6
)
View
the
displayed
value
of
U0
-
21
and
save
the
value
to
AC
-
03
.
At
correction
of
AI2
and
AI3
,
the
actually
sampled
voltage
is
respectively
queried
in
U0
-
22
and
U0
-
23
.
For
AI1
and
AI2
,
2
V
and
8
V
are
suggested
as
the
correction
voltages
.
For
AI3
, -
8
V
and
8
V
are
suggested
.
Summary of Contents for VDF650 Series
Page 1: ...VDF650 Series High Performance AC Drive...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions VDF650 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information VDF650 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions VDF650 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...