Description
of
Function
Codes
VDF650
User
Manual
-
154
-
For
CLVC
,
it
is
used
to
adjust
the
output
current
of
the
AC
drive
with
same
load
.
Function
Code
Parameter
Name
Setting
Range
Default
P2
-
07
Time
constant
of
speed
loop
flter
0
.
000
–
0
.
100s
0
.
000s
In the vector control mode
,
the output of the speed loop regulator is torque current
reference
.
This
parameter is
used to
flter
the torque references
.
It
need not
be adjusted
generally
and
can
be
increased
in
the
case
of
large
speed
fuctuation
.
In
the
case
of
motor
oscillation
,
decrease
the
value
of
this
parameter
properly
.
If the value of this parameter is small
,
the output torque of the AC drive may fluctuate
greatly
,
but
the
response
is
quick
.
Function
Code
Parameter
Name
Setting
Range
Default
P2
-
08
Vector
control
over
-
excitation
gain
0
–
200
64
During deceleration of the AC drive
,
over
-
excitation control can restrain rise of the bus
voltage
to
avoid
the
overvoltage
fault
.
The
larger
the
over
-
excitation
gain
is
,
the
better
the
restraining
effect
is
.
Increase the over
-
excitation gain if the AC drive is liable to overvoltage error during
deceleration
.
Too large over
-
excitation gain
,
however
,
may lead to an increase in output
current
.
Therefore
,
set
this
parameter
to
a
proper
value
in
actual
applications
.
Set
the
over
-
excitation
gain
to
0
in
applications
of
small
inertia
(
the
bus
voltage
will
not
rise
during
deceleration
)
or
where
there
is
a
braking
resistor
.
Function
Code
Parameter
Name
Setting
Range
Default
P2
-
09
Torque
upper
limit
source
in
speed
control
mode
0
:
P2
-
10
1
:
AI1
2
:
AI2
3
:
AI3
4
:
Pulse
setting
(
DI5
)
5
:
Communication
setting
0
P2
-
10
Digital
setting
of
torque
upper
limit
in
speed
control
mode
0
.
0
%–
200
.
0
%
150
.
0
%
In
the
speed
control
mode
,
the
maximum
output
torque
of
the
AC
drive
is
restricted
by
P2
-
09
.
If
the
torque
upper
limit
is
analog
,
pulse
or
communication
setting
,
100
%
of
the
setting
corresponds
to
the
value
of
P2
-
10
,
and
100
%
of
the
value
of
P2
-
10
corresponds
to
the
AC
drive
rated
torque
.
For
details
on
the
AI1
,
AI2
and
AI3
setting
,
see
the
description
of
the
AI
curves
in
group
P4
.
For
details
on
the
pulse
setting
,
see
the
description
of
P4
-
28
to
P4
-
32
.
When
the
AC
drive
is
in
communication
with
the
master
,
if
P2
-
09
is
set
to
5
“
communication
setting
”,
P2
-
10
“
Digital setting
of
torque upper limit in speed control
mode
”
can be
set
via
communication
from
the
master
.
In other conditions
,
the host computer writes data
-
100
.
00
%
to 100
.
00
%
by the
communication address 0x1000
,
where 100
.
0
%
corresponds to the value of P2
-
10
.
The
communication
protocol
can
be
Modbus
,
CANopen
,
CANlink
or
PROFIBUS
-
DP
.
Summary of Contents for VDF650 Series
Page 1: ...VDF650 Series High Performance AC Drive...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions VDF650 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information VDF650 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions VDF650 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...