Description
of
Function
Codes
VDF650
User
Manual
-
150
-
Function
Code
Parameter
Name
Setting
Range
Default
P1
-
28
Encoder
type
0
:
ABZ
incremental
encoder
1
:
UVW
incremental
encoder
2
:
Resolver
3
:
SIN
/
COS
encoder
4
:
Wire
-
saving
UVW
encoder
0
The
VDF650
supports
multiple
types
of
encoder
.
Different
PG
cards
are
required
for
different
types of encoder
.
Select the appropriate PG card for the encoder used
.
Any of the five
encoder types is applicable to synchronous motor
.
Only ABZ incremental encoder and
resolver
are
applicable
to
asynchronous
motor
.
After
installation
of
the
PG
card
is
complete
,
set
this
parameter
properly
based
on
the
actual
condition
.
Otherwise
,
the
AC
drive
cannot
run
properly
.
Function
Code
Parameter
Name
Setting
Range
Default
P1
-
30
A
/
B
phase
sequence
of
ABZ
incremental
encoder
0
:
Forward
1
:
Reserve
0
This
parameter
is
valid
only
for
ABZ
incremental
encoder
(
P1
-
28
=
0
)
and
is
used
to
set
the
A
/
B
phase
sequence
of
the
ABZ
incremental
encoder
.
It is valid for
both
asynchronous
motor
and
synchronous
motor
.
The
A
/
B
phase
sequence
can be obtained through
"
Asynchronous motor complete auto
-
tuning
"
or
"
Synchronous
motor
no
-
load
auto
-
tuning
".
Function
Code
Parameter
Name
Setting
Range
Default
P1
-
31
Encoder
installation
angle
0
.
0
°–
359
.
9
°
0
.
0
°
This parameter is applicable only to synchronous motor
.
It is valid for ABZ incremental
encoder
,
UVW
incremental
encoder
,
resolver
and
wire
-
saving
UVW
encoder
,
but
invalid
for
SIN
/
COS
encoder
.
It
can
be
obtained
through
synchronous
motor
no
-
load
auto
-
turning
or
with
-
load
auto
-
tuning
.
After
installation
of
the
synchronous
motor
is
complete
,
the
value
of
this
parameter
must
be
obtained
by
motor
auto
-
tuning
.
Otherwise
,
the
motor
cannot
run
properly
.
Function
Code
Parameter
Name
Setting
Range
Default
P1
-
32
U
,
V
,
W
phase
sequence
of
UVW
encoder
0
:
Forward
1
:
Reverse
0
P1
-
33
UVW
encoder
angle
offset
0
.
0
°–
359
.
9
°
0
.
0
°
These two
parameters
are
valid
only when
the
UVW
encoder
is
applied
to
a
synchronous
motor
.
They
can
be
obtained
by
synchronous
motor
no
-
load
auto
-
tuning
or
with
-
load
auto
-
tuning
.
After installation of the synchronous motor is complete
,
the values of these two
parameters must be obtained by motor auto
-
tuning
.
Otherwise
,
the motor cannot run
properly
.
Summary of Contents for VDF650 Series
Page 1: ...VDF650 Series High Performance AC Drive...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions VDF650 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information VDF650 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions VDF650 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...