Operation
,
Display
and
Application
Examples
VDF650
User
Manual
-
70
-
4
.
9
.
2
Motor
Auto
-
tuning
To obtain the motor parameters
,
the AC drive can perform dynamic auto
-
tuning or static
auto
-
tuning
.
For the
asynchronous
motor that cannot
be
disconnected
from the
load
,
you
can
input
the
motor
parameters
of
the
same
model
that
was
successfully
auto
-
tuned
before
.
Auto
-
tuning
Application
Result
No
-
load
dynamic
auto
-
tuning
It
is
applied
to
applications
where
the
motor
(
synchronous
motor
or
asynchronous
motor
)
can
be
disconnected
from
the
load
.
Best
With
-
load
dynamic
auto
-
tuning
It
is
applied
to
applications
where
the
motor
(
synchronous
motor
or
asynchronous
motor
)
cannot
be
disconnected
from
the
load
.
OK
Static
auto
-
tuning
It
is
applied
to
applications
where
the
motor
(
asynchronous
motor
only
)
cannot
be
disconnected
from
the
load
and
dynamic
auto
-
tuning
is
not
allowed
.
Poor
Manual
input
It
is
applied
to
applications
where
the
motor
(
asynchronous
motor
only
)
cannot
be
disconnected
from
the
load
.
Input
the
motor
parameters
of
the
same
model
that
was
successfully
auto
-
tuned
before
into
function
codes
P1
-
00
to
P1
-
10
.
OK
The
following
motor
auto
-
tuning
description
takes
motor
1
as
an
example
.
The
auto
-
tuning
of
motor
2
,
3
,
and
4
is
the
same
and
only
the
function
codes
are
changed
correspondingly
.
The
process
of
motor
auto
-
tuning
is
as
follows
:
1
)
If
the
motor
can
be
disconnected
from
the
load
,
disconnect
the
motor
from
the
load
mechanically
after
power
-
off
so
that
the
motor
can
run
without
load
.
2
)
After
power
-
on
,
set
P0
-
02
(
Command
source
selection
)
to
0
(
Operation
panel
control
).
3
)
Input
the
motor
nameplate
parameters
(
such
as
P1
-
00
to
P1
-
05
)
correctly
and
input
the
following
parameters
based
on
the
actually
selected
motor
.
Motor
Parameter
Motor
1
P1
-
00
:
Motor
type
selection
P1
-
01
:
Rated
motor
power
P1
-
02
:
Rated
motor
voltage
P1
-
03
:
Rated
motor
current
P1
-
04
:
Rated
motor
frequency
P1
-
05
:
Rated
motor
rotational
speed
Motor
2
A2
-
00
to
A2
-
05
,
defned
the
same
as
P1
-
00
to
P1
-
05
Motor3
A3
-
00
to
A3
-
05
,
defned
the
same
as
P1
-
00
to
P1
-
05
Motor
4
A4
-
00
to
A4
-
05
,
defned
the
same
as
P1
-
00
to
P1
-
05
For asynchronous motor
,
set P1
-
37
(
Auto
-
tuning selection
)
to 2
(
Asynchronous motor
complete
auto
-
tuning
).
For
motors
2
,
3
,
or
4
,
the
corresponding
function
code
is
A2
-
37
/
A3
-
37
/
A4
-
37
.
Press
ENTER
on the operation panel. The operation panel displays:
Summary of Contents for VDF650 Series
Page 1: ...VDF650 Series High Performance AC Drive...
Page 9: ......
Page 10: ...1 Safety Information and Precautions...
Page 17: ...Safety Information and Precautions VDF650 User Manual 16...
Page 18: ...2 Product Information...
Page 29: ...Product Information VDF650 User Manual 28...
Page 30: ...3 Mechanical and Electrical Installation...
Page 46: ...4 Operation Display and Application Examples...
Page 79: ...Operation Display and Application Examples VDF650 User Manual 78...
Page 80: ...5 Function Code Table...
Page 136: ...6 Description of Function Codes...
Page 248: ...7 EMC...
Page 260: ...8 Selection and Dimensions...
Page 285: ...Selection and Dimensions VDF650 User Manual 284...
Page 286: ...9 Maintenance and Troubleshooting...