46
•
vacon
monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
NOTE:
These parameters are shown when
P17.2 = 0.
5.18 Motor c (Control panel: Menu PAR -> P16)
5.19 Easy usage menu (Control panel: Menu PAR -> P17)
P15.22
Temperature
min value
-50.0/
223.2
P15.23
0.0
1706
Temperature min value for
PID and frequency refer-
ence scale; hidden until an
OPTBH board is connected
P15.23
Temperature
max value
P15.22
200.0/
473.2
100.0
1707
Temperature max value for
PID and frequency refer-
ence scale; hidden until an
OPTBH board is connected
Code
Parameter
Min
Max
Unit
Default
ID
Note
P16.1
Motor Preheat
Function
0
2
0
1225
0 =
Not used
1 =
Always in stop state
2 =
Controlled by digital
input
P16.2
Motor Preheat
Current
0
0.5 x
I
Nunit
A
0
1227
DC current for preheating
motor and drive in stop
state. Active in stop state
or by digital input while in
stop state.
Table 18: Motor Preheat
Code
Parameter
Min
Max
Unit
Default
ID
Note
Application Type
0
3
0
540
0 =
Basic
1 =
Pump
2 =
Fan drive
3 =
High Torque
NOTE:
Visible only when
the startup wizard is
active.
P17.2
Parameter con-
ceal
0
1
1
115
0
= All parameters visible
1
= Only quick setup
parameter group visible
P17.3
Temperature
unit
0
1
0
1197
0
= Celsius
1
= Kelvin
NOTE:
Hidden until an
OPTBH board is connected
Table 19: Easy usage menu parameters
Code
Parameter
Min
Max
Unit Default
ID
Note
Table 17: PID control parameters
P17.1