monitoring & parameters
vacon
•
39
24-hour s358 (0)201 212 575 • Email: [email protected]
5
5.12 Fieldbus Data-Mapping (Control panel: Menu PAR -> P10)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P10.1
FB Data Output 1
selection
0
Varies
0
852
0
= Frequency reference
1
= Output reference
2
= Motor speed
3
= Motor current
4
= Motor voltage
5
= Motor torque
6
= Motor power
7
= DC link voltage
8
= Active fault code
9
= Analog AI1
10
= Analog AI2
11
= Digital input state
12
= PID feedback value
13
= PID setpoint
14
= Pulse train/encoder
input(%)
15
= Pulse train/encoder
pulse()
16
= AIE1
P10.2
FB Data Output 2
selection
0
Varies
1
853 Variable mapped on PD2
P10.3
FB Data Output 3
selection
0
Varies
2
854 Variable mapped on PD3
P10.4
FB Data Output 4
selection
0
Varies
4
855 Variable mapped on PD4
P10.5
FB Data Output 5
selection
0
Varies
5
856 Variable mapped on PD5
P10.6
FB Data Output 6
selection
0
Varies
3
857 Variable mapped on PD6
P10.7
FB Data Output 7
selection
0
Varies
6
858 Variable mapped on PD7
P10.8
FB Data Output 8
selection
0
Varies
7
859 Variable mapped on PD8
P10.9
Aux CW Data In
selection
0
5
0
1167
PDI for Aux CW
0
= Not used
1
= PDI1
2
= PDI2
3
= PDI3
4
= PDI4
5
= PDI5
Table 12: Fieldbus Data-Mapping