5
5.13 Prohibited Frequencies (Control panel: Menu PAR -> P11)
5.14 Limit Supervisions (Control panel: Menu PAR -> P12)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P11.1
Prohibit Frequency
Range 1 Low Limit
0.00
P3.2
Hz
0.00
509
Low Limit
0.00 = Not used
P11.2
Prohibit Frequency
Range 1 High Limit
0.00
P3.2
Hz
0.00
510
High Limit
0.00 = Not used
P11.3
Prohibit Frequency
Range 2 Low Limit
0.00
P3.2
Hz
0.00
511
Low Limit
0.00 = Not used
P11.4
Prohibit Frequency
Range 2 High Limit
0.00
P3.2
Hz
0.00
512
High Limit
0.00 = Not used
Table 13: Prohibited Frequencies
Code
Parameter
Min
Max
Unit
Default
ID
Note
P12.1
Output freq
supervision func-
tion
0
2
0
315
0
= Not used
1
= Low limit
2
= High limit
P12.2
Output freq
supervision limit
0.00
P3.2
Hz
0.00
316
Output frequency super-
vision threshold
P12.3
Torque supervi-
sion function
0
2
0
348
0
= Not used
1
= Low limit
2
= High limit
P12.4
Torque supervi-
sion limit
0.0
300.0
%
0.0
349
Torque supervision
threshold
P12.5
Unit Temperature
Supervision
0
2
0
354
0
= Not used
1
= Low limit
2
= High limit
P12.6
Unit Temperature
Supervision Limit
-10
100
°C
40
355
Unit temperature super-
vision threshold
P12.7
Analog input
superv signal
0
Varies
0
356
0
= AI1
1
= AI2
2
= AIE1
P12.8 AI superv ON level
0.00
100.00
%
80.00
357 ON threshold AI superv.
P12.9
AI superv OFF
level
0.00
100.00
%
40.00
358 OFF threshold AI superv.
Table 14: Limit Supervisions