monitoring & parameters
vacon
•
29
24-hour s358 (0)201 212 575 • Email: [email protected]
5
5.4 Start/stop setup (Control panel: Menu PAR -> P2)
Code
Parameter
Min
Max
Unit Default
ID
Note
P2.1
Remote Control
Place Selection
0
2
0
172
0
= I/O terminals
1
= Fieldbus
2
= Keypad
Start function
0
1
0
505
0
= Ramp
1
= Flying start
Stop function
0
1
0
506
0
= Coasting
1
= Ramp
P2.4
I/O Start/Stop
logic
0
4
2
300
I / O control I / O control
signal 1 signal 2
0
Forward Reverse
1
Fwd(edge) Inverted Stop
2
Fwd(edge) Rev(edge)
3
Start Reverse
P2.5
Local / Remote
0
1
0
211
0
= Remote control
1
= Local control
P2.6
Keypad control
direction
0
1
0
123
0
= Forward
1
= Reverse
P2.7
Keypad stop but-
ton
0
1
1
114
0
= Keypad control only
1
= Always
P2.8
Remote Control
Place 2 Selection
0
2
0
173
0
= I/O terminals
1
= Fieldbus
2
= Keypad
keypad button
lock
0
1
0
15520
0
= Unlock all keypad button
1
= Loc/Rem button locked
Table 4: Start/stop setup
P2.2
P2.3
P2.9