Brake Chopper
0
2
0
504
0
= Disabled
1
= Enabled: Always
2
= Run state
Brake chopper
level
0
911
V
Varies
1267
Brake chopper control acti-
vation level in volt.
For 240 V supply:
240*1.35*1.18 = 382 V
For 400V supply:
400*1.35*1.18 = 638V
Please note that when the
brake chopper is used the
overvoltage controller can
be switched off or the over-
voltage reference level can
be set higher than the
brake chopper level.
Motor identifica-
tion
0
2
0
631
0
= Not active
1
= Standstill identification
(need run command within
20 s to activate)
2
= Identification with run
(need run command within
20 s to activate.
Only available in power SW
V026 included in
FW01070V010 or later ver-
sion)
Rs voltage drop
0.00
100.0
0
%
0.00
662
Voltage drop over motor
windings as % of U
nmot
at
nominal current.
Overvoltage con-
troller
0
2
1
607
0
= Disabled
1
= Enabled, Standard
mode
2
= Enabled, Shock load
mode
Undervoltage
controller
0
1
1
608
0
= Disable
1
= Enable
Sine filter
0
1
0
522
0
= Not in use
1
= In use
Code
Parameter
Min
Max
Unit Default
ID
Note