monitoring & parameters
vacon
•
43
24-hour s358 (0)201 212 575 • Email: [email protected]
5
NOTE:
* These parameters are only available in power SW FWP00001V026 included in
FW01070V010 or later version.
NOTE:
These parameters are shown when
P17.2 = 0.
5.16 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE:
These parameters are shown when
P17.2 = 0.
P13.25
Temperature fault
input
1
7
1
739
Binary code selection of
signals to use for alarm
and fault triggering
B0
= Temperature input 1
B1
= Temperature input 2
B2
= Temperature input 3
NOTE:
Hidden until an
OPTBH board is con-
nected
P13.26
Temperature fault
mode
0
2
2
743
0
= Not used
1
= Low limit
2
= High limit
P13.27
Temperature fault
limit
-50.0/
223.2
200.0/
473.2
100.0
742
Temperature fault
threshold; hidden until
an OPTBH board is con-
nected
Input phase fault*
0
3
3
730 As parameter P13.3
Motor tempera-
ture memory
mode*
0
2
2
15521
0 =
disabled
1 =
constant mode
2 =
last value mode
Code
Parameter
Min
Max
Unit Default ID
Note
Automatic Reset
0
1
0
731
0
= Disabled
1
= Enable
Wait time
0.10
10.00
s
0.50
717 Waiting time after fault
Trial time
0.00
60.00
s
30.00
718 Maximum time for trials
Trials number
1
10
3
759 Maximum trials
Restart Function
0
2
2
719
0
= Ramping
1
= Flying
2
= From Start Function
Table 16: Fault autoreset parameters
Code
Parameter
Min
Max
Unit
Default
ID
Note
Table 15: Protections
P13.28
P13.29
P14.1
P14.2
P14.3
P14.4
P14.5