34
•
vacon
monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
5.8 Analog inputs (Control panel: Menu PAR -> P6)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P6.1
AI1 Signal range
0
1
0
379
0
= 0 - 100% ( 0 - 10 V)
1
= 20% - 100% ( 2 - 10 V)
P6.2
AI1 Custom min
-100.00
100.00
%
0.00
380 0.00 = No min scaling
P6.3
AI1 Custom max
-100.00
300.00
%
100.00
381 100.00 = No max scaling
P6.4
AI1 filter time
0.0
10.0
s
0.1
378 0 = no filtering
P6.5
AI2 signal range
0
1
0
390 See P6.1
P6.6
AI2 Custom min
-100.00
100.00
%
0.00
391 See P6.2
P6.7
AI2 Custom max
-100.00
300.00
%
100.00
392 See P6.3
P6.8
AI2 filter time
0.0
10.0
s
0.1
389 See P6.4
P6.9 AIE1 Signal range
0
1
0
143
See P6.1, hidden until an
option board is con-
nected
P6.10 AIE1 Custom Min
-100.00 100.00
%
0.00
144
See P6.2, hidden until an
option board is con-
nected
P6.11 AIE1 Custom Max
-100.00 300.00
%
100.00
145
See P6.3, hidden until an
option board is con-
nected
P6.12
AIE1 Filter time
0.0
10.0
s
0.1
142
See P6.4, hidden until an
option board is con-
nected
Table 8: Analog inputs