VersaPro Temperature Controller
Page 69
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
BLOCK 0
HEX
DEC
PARAMETER
DESCRIPTION
READ/WRITE
determine the real alarm value.
Range = -999 to 9999.
Default = 0000
08 8
ALRMMD1
Alarm 1 configuration
BITS 0 – 3
0000 = OFF (DEFAULT)
0001 = DEVIATION BAND
0010 = BAND LOW
0011 = BAND HIGH
0100 = PERCENT OUT LOW
0101 = PERCENT OUT HIGH
0110 = FULL SCALE LOW
0111 = FULL SCALE HIGH
1000 = PROBE IMPEDANCE / VERIFY
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = START
1101 = SOAK
1110 = TIMER
1111 = FAULT
BIT 4 ACTION CONTROL
0 = DIRECT
1 = REVERSE
BIT 5 NO LATCH = 0, LATCHED = 1
BIT 6 – 15 SPARE
READ ONLY
09 9
ALRMMD2
Alarm 2 configuration
BITS 0 – 3
0000 = OFF (DEFAULT)
0001 = DEVIATION BAND
0010 = BAND LOW
0011 = BAND HIGH
0100 = PERCENT OUT LOW
0101 = PERCENT OUT HIGH
0110 = FULL SCALE LOW
0111 = FULL SCALE HIGH
1000 = PROBE IMPEDANCE / VERIFY
1001 = SPARE
1010 = SPARE
1011 = SPARE
1100 = START
1101 = SOAK
1110 = TIMER
1111 = FAULT
READ ONLY