Installation
The VersaPro instrument is designed for up to 1/8" panel mounting in a DIN standard opening of 3.62" square
(adapter panels available by special order). Required rear clearance is 7.5” to allow for wiring.
As with all solid state equipment, the controller should be located away from excessive heat, humidity, and
vibration. Since the unit uses LED and LCD display devices, it should also be located so that direct sunlight
will not interfere with the display's visibility. The instrument requires 120/240 VAC 50/60 Hz and should not be
on the same circuit with other noise-producing equipment such as induction machines, large electrical motors,
etc. Signal wiring must be run separate from control wiring. It is suggested that signal wiring at the rear
terminals of the instrument be routed in one direction (up or down) while the AC power wires are routed in the
opposite direction.
The following figure shows the rear terminals locations on the rear of the VersaPro.
Figure 1 VersaPro Rear Panel
The following figure shows a typical wiring schematic for the Versapro temperature controller.