VersaPro Temperature Controller
Page 29
Copyright © 2013, United Process Controls Inc.
All rights to copy, reproduce and transmit are reserved
Parameter Name
Units or Options
Range
Description
HIPO – Output High,
this alarm
sets the threshold for the
maximum control output allowed
which is set by ALARM 1 VALUE.
LOPO – Output Low,
this alarm
sets the threshold for the
minimum control output allowed
which is set by ALARM 1 VALUE.
FALt – Fault
, open inputs for mV,
thermocouple or hardware fault.
Prob – Probe
, fault active if
impedance or verification are out
of range.
tinE – Time
, establishes alarm
contact as the contact used for
the End alarm.
Strt – Start
, same as Time.
SOAk – Soak
, same as Time.
ALARM 1 VALUE
Trigger setpoint value
ALARM 1 ACTION
REV, LREV, DIR, LDIR
REV = Reverse (N.C.) can be
acknowledged even if the
condition still exists.
LREV = Latched Reverse (N.C.)
can not be acknowledged if the
condition still exists.
DIR = Direct (N.O.) can be
acknowledged even if the
condition still exists.
LDIR = Latched Direct (N.C.) can
not be acknowledged if the
condition still exists.
ALRM 1 TM ON DLY
0 – 250 SECONDS
Delay ON time for ALARM1
ALRM 1 TMOFF DLY
0 – 250 SECONDS
Delay OFF time for ALARM1
ALARM 2 TYPE
Same as ALARM 1
TYPE
Same as ALARM 1 TYPE
ALARM 2 VALUE
Trigger setpoint value
ALARM 2 ACTION
Same as ALARM 1 ACTION
ALRM 2 TM ON DLY
0 – 250 SECONDS
Delay ON time for ALARM2
ALRM 2 TMOFF DLY
0 – 250 SECONDS
Delay OFF time for ALARM2
Table 8 Communication Menu (HOST)
Parameter Name
Units or Options
Range
Description
PROTOCOL
PROP OR BUSS
PROP is Marathon Monitors,
Inc. protocol,
BUSS is Modbus
ADDRESS
1 TO 15 (MSI)
1 TO 255 (MOD)