Space Temperature
Alarm Set Points
High Setpoint > 85.0 °F
Low Setpoint > 60.0 °F
Enable High > Yes
Enable Low > No
Alarm Delay > 060sec
Depending on the setup, Return Temperature or Space
Temperature, there are specific High and Low Alarm Set
Points both having enable points for high and low alarm
The Enable High and/or Enable Low must be set to Yes
in order to the High and/or Low Alarm to trigger when the
temperature rises above or falls below the Alarm Set Point
The Temperature must also remain above or below the
Alarm Set Point for the Alarm Delay before the Alarm will
occur
U01
Return Humidity
Alarm Set Points
High Setpoint > 60.0 °F
Low Setpoint > 20.0 °F
Enable High > Yes
Enable Low > No
Alarm Delay > 060sec
U01
Space Humidity
Alarm Set Points
High Setpoint > 60.0 °F
Low Setpoint > 20.0 °F
Enable High > Yes
Enable Low > No
Alarm Delay > 060sec
Depending on the setup, Return Humidity or Space
Humidity, there are specific High and Low Alarm Set Points
both having enable points for high and low alarm The
Enable High and/or Enable Low must be set to Yes in order
to the High and/or Low Alarm to trigger when the humidity
rises above or falls below the Alarm Set Point The Humidity
must also remain above or below the Alarm Set Point for the
Alarm Delay before the Alarm will occur
U01 Supply Temperature
Alarm Set Points
High Setpoint > 80.0 °F
Low Setpoint > 40.0 °F
Enable High > Yes
Enable Low > Yes
Alarm Delay > 060sec
For Supply Temperature there are specific High and Low
Alarm Set Points both having enable points for high and low
alarm The Enable High and/or Enable Low must be set to
Yes in order to the High and/or Low Alarm to trigger when
the temperature rises above or falls below the Alarm Set
Point The Temperature must also remain above or below
the Alarm Set Point for the Alarm Delay before the Alarm
will occur