Installation, Operation and Maintenance Manual
Marvel Mini
52
Subject to change without notice.
120.9-IM (1218)
number of days between rotations to the next unit And
allow the system to know in applications with 3 or greater
units in a network if any units should remain on continuously
without rotating to the off or stand-by position
Technician Menu 04
>>>Manual Control <<<
/
Scroll Up/Down
Enter Selected Menu
Esc to Previous
The Manual Control sub-menu allows technicians the ability
to manually turn components on or off, manually adjust
modulating output devices, and manually adjust sensor
readings all to be able to test a unit and/or system
Technician Menu 05
>>>Sensor Setup <<<
/
Scroll Up/Down
Enter Selected Menu
Esc to Previous
Sensor Setup is a sub-menu that allows technicians to
calibrate sensor readings, set up custom sensors, add a field
purchased (consult factory first) sensor in the event that the
customer has a failed sensor and a critical application that
the unit needs to be running that same day and they cannot
wait for a factory supplied original sensor It also allows
adjustment of Minimum and Maximum output settings for
the Modulating Analog Output devices connected to the
controller
Technician Menu 06
>>>Digital Inputs <<<
/
Scroll Up/Down
Enter Selected Menu
Esc to Previous
The Digital Inputs sub-menu is used to set the direction
(normally open or normally closed) any interconnected
devices are desired to alarm, be active, or inactive
IMPORTANT!
Please do not adjust factory provided
devices. Primarily only field provided components should
be adjusted based on the direction the component is active
(open or closed)
Technician Menu 07
>>>Economizer <<<
/
Scroll Up/Down
Enter Selected Menu
Esc to Previous
The Economizer sub-menu allows customer to adjust the
settings with Airside and Waterside Economizer
Technician Menu 08
>>>Blower VFDs <<<
/
Scroll Up/Down
Enter Selected Menu
Esc to Previous