Installation, Operation and Maintenance Manual
Marvel Mini
60
Subject to change without notice.
120.9-IM (1218)
For all other sensor terminations, please refer to the
electrical diagrams provided with the units for electrical
connections
Digital Outputs
Relays on a Marvel controller are capable of handling up to
10 Amps Resistive at 1 Amp Inductive loading at 250 VAC to
control any of the Digital Output functions listed on page 5
To power a control device (contactor, starter, solenoid coil,
etc) connect the neutral side of the 24 VAC power supply
to the control device Connect the hot side of the 24 VAC
power supply through the common C(x) of the digital output
relay as shown in Figure 18 – Digital Output Termination
References
FIGURE 18 – DIGITAL OUTPUT TERMINATION REFERENCES
Analog Outputs
The Analog Outputs on a Marvel controller are capable of
providing modulating output voltage of 0 – 10 VDC to control
any of the following Analog Outputs listed on page 4 The
analogs outputs must be powered externally using 24 VAC
The neutral side of the 24 VAC power supply is connected to
terminal VG0 The 24VAC hot side is connected to terminal
VG1 Analog Output 1 through Analog Output 6 (Y1 through
Y6 respectively) connects to the modulating output for the
device being controlled Refer to Figure 19 – Analog Output
Termination References for connection details
FIGURE 19 – ANALOG OUTPUT TERMINATION
REFERENCES
OPTIONAL BOARDS
Building Management Systems (BMS
Systems)
Several methods of supervisory systems may be used to
communicate with the Marvel Main Board which allow for
monitoring of the systems readings, changing/offsetting of
set points and remotely view alarm status The following is
a list of BMS Systems the Marvel Control can interface with:
BACnet
TM
ModBus®
LonWorks® pCOWeb