Installation, Operation and Maintenance Manual
Marvel Mini
48
Subject to change without notice.
120.9-IM (1218)
U01
Schedule Monday
(hh:mm)
Occupied > 7:00
Unoccupied > 20:00
Once the Day of the Week has been enabled for the
Occupancy Schedule to occur, the screen for that day will
appear within the Schedule sub-menu Simply setting the
Occupied and Unoccupied times will allow the controller
to follow the schedule for that day of the week Should
Monday and Wednesday have an Occupied Times but
Tuesday is disabled, the unit will go into occupied during the
occupied start time and then go into unoccupied and remain
unoccupied until the occupied start time on Wednesday
Set Back ON and OFF Times
Should Set Back be enabled under the Set Back Menu, the
Set Back Schedule will appear here under the Schedule
sub-menu
U01
Set-Back Monday
(hh:mm)
Setback ON >18:00
Setback OFF>20:00
The Set Back ON is the Start time for the unit to be in the
Set Back Mode The Set Back OFF is the stop time for Set
Back Mode The unit will either go back into Occupied Mode
or into Unoccupied Mode depending on how the Schedule
is set up The Set Back Set Points for Cooling, Heating,
Humidification, and Dehumidification all appear under the
Set Back Menu
Morning Warm-Up
U01 Warm-Up Start Time
(hh:mm)
Monday
> 6:00
Tuesday
> 6:00
Wednesday > 6:00
Thursday > 6:00
Friday
> 6:00
U01 Warm-Up Start Time
(hh:mm)
Saturday > 6:00
Sunday
> 6:00
Duration > 60min
If Morning Warm-Up is enabled, the Morning Warm-Up Start
Time will appear under the Schedule sub-menu for each
Day of the Week There is also a Duration Time in minutes
that needs to be set The Morning Warm-Up then starts at
the Warm-Up Start Time for that particular Day and be in
Morning Warm-Up Mode until either the Warm-Up Set Point
is achieved or until the Duration Time expires
Morning Cool-Down
U01 Cool-down Start Time
(hh:mm)
Monday
> 6:00
Tuesday > 6:00
Wednesday > 6:00
Thursday > 6:00
Friday
> 6:00