Installation, Operation and Maintenance Manual
Marvel Mini
58
Subject to change without notice.
120.9-IM (1218)
BLOWER VFDS
U01
Duct Pressure
Proportional > 0.030
Integrations > 30sec
Derivative > 5sec
Cycle Time > 1500msec
Low Limit
> 30.0%
High Limit > 100.0%
The Blower VFDs sub-menus allow for adjustment of
the settings for variable air volume duct pressure control
settings Low Limit is the minimum speed in percent that
the blowers will operate The Low Limit must be a minimum
of 30% and not less than 30% as the system requires a
minimum 30% for proper cooling The High Limit may be
limited to a value less than 100% due to the blower size
Please consult United CoolAir before adjusting these
settings
CHANGE PASSWORDS
The Enable Password screens allow for enabling of the
Basic and/or Technician Passwords The passwords can be
a value between 0 and 9999 Please record the passwords
if installed
U01
Enable Passwords
Basic User>Disable
Technician>Enable
U01
Enable Passwords
Basic User>0000
Technician>9995
SYSTEM INFORMATION
U01
Information
United CoolAir
Marvel Premium Controller
Version
>1.1.00 1 Op
System>4.1.005
U01
Information
United CoolAir
Marvel Premium Controller
Job Number>026479 Op
System >4.1.005
The Information Screens above are displayed based on
either a Version Number or by a Job Number If the software
is a standard version, the verbiage “Version” will be displayed
followed by the version number Should the system have
custom software, the verbiage “Job Number” followed by
the United CoolAir Job Number will be displayed On the
last line, the Operating System version is displayed