UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 19
Revision 7/06.12
Of 47
∗
Fault in controllable output
The right screen section “12” contains the number of the
controllable outputs in fault condition.
∗
Fault in mains power supply
The backlight of the LCD is extinguished and is
activated only if a button is pressed. 15 s after that the
light is extinguished again.
∗
Backup battery fault.
∗
Fault in external devices power supply
∗
Short circuit in ground wire
∗
Fault in internal power supply
∗
Fault in the charger
10.3. Using the keypad
In
System error
and in
Low battery due to interrupted mains supply
conditions none of the buttons
is active. For the rest of the fault conditions 6 active buttons are supported. When the fire control
panel operates in combination of other conditions, their buttons are active too.
10.3.1. Button
(Stop Alarm)
Press the button to:
−
Switch off the local sounder for fire condition/pre-fire condition, if there are fire alarm lines, in
Fire Condition or Pre-Fire Condition;
−
Switch off the local sounder for fault condition when a Fault Condition is detected;
−
Switch off the outputs associated to the lines in Fire Condition;
−
Switch on the LED indicator of the button, if signaling or outputs for fire condition have been
switched off.
The button does not affect nor is its action cancelled by the following events:
−
When Fire Condition is registered in a new line, or transition from Fire condition stage I to Fire
condition stage II shall activate the local sounder for Fire/Pre-Fire condition and shall switch
on the lines associated to the corresponding outputs;
−
When Pre-Fire Condition is registered in a new line, the local sounder for Fire/Pre-Fire
condition shall be activated;
−
A new Fault condition shall activate the local sounder for Fault condition only.
The button’s LED indicator remains illuminated if the signalization and/or outputs remain off.
The button is active at Access level 2 (the key on the front panel is in position
).
10.3.2. Button
(Start Alarm)
Press the button (at Access level 2) to cancel the operation of button
, i.e. the signalization
and the outputs that have been switched off by this button are activated and its LED indicator is
extinguished.
Note: When the fire control panel operates in a combination of Pre-Fire condition and Fire
condition, the button triggers other operations (see section 8.3.3).
Flt: Charger
Flt: Uintrn
Flt: Earth
Flt: Uuser
Flt: Battery
Flt: MainPow 220V
Flt: cO
12