Press the button to:
−
Switch off the local sounder for fire condition/pre-fire condition, if there are fire alarm lines, in
which the fire control panel has detected Fire Condition or Pre-Fire Condition;
−
Switch off the local sounder for fault condition when a Fault Condition is detected;
−
Switch off the outputs associated to the lines in Fire Condition;
−
Switch on the LED indicator of the button, if signaling or outputs for fire condition have been
switched off.
The button does not affect nor is its action cancelled by the following events:
−
When Fire Condition is registered in a new line, or transition from Fire condition stage I to Fire
condition stage II shall activate the local sounder for Fire/Pre-Fire condition and shall switch
on the lines associated to the corresponding outputs;
−
When Pre-Fire Condition is registered in a new line, the local sounder for Fire/Pre-Fire
condition shall be activated;
−
A new Fault condition shall activate the local sounder for Fault condition only.
The button’s LED indicator remains illuminated if the signalization and/or outputs remain off.
The button is active at Access level 2 (the key on the front panel is in position
).
9.3.2. Button
(Start Alarm)
Press the button (at Access level 2) to cancel the operation of button
, i.e. the signalization
and the outputs that have been switched off by this button are activated and its LED indicator is
extinguished.
Note: When the fire control panel operates in a combination of Pre-Fire condition and Fire
condition, the button triggers other operations.(see section 8.3.3).
9.3.3. Button
(Menu)
Press the button to enter Information and Control Mode.
10. Fault Condition
10.1. Description
The fire control panel enters Fault Condition when any of the events below has been registered:
−
System error;
−
Circuit boards conflict;
−
Backup batteries discharged due to mains supply interruption;
−
Fault in a line – removed fire detector, short circuit or break;
−
Fault in a controllable output – short circuit or break;
−
Fault in main supply;
−
Fault in backup batteries power supply;
−
Fault in external devices power supply;
−
Short circuit in grounded wire;
−
Fault in internal power supply;
−
Fault in the charger.
The
System error
is a fatal error – the fire control panel does not service lines, outputs either
peripherals. You can exit the fault condition if you disconnect the control panel from the main supply
and send it for repairs.
The
Circuit
boards conflict
is also a fatal error, but you can exit the condition by entering SetUp
Mode. Such fault condition occurs usually after modification of the physical configuration of the fire
control panel – addition, removal or replacement of additional module.
The
discharge of the backup batteries due to mains supply interruption
is also a fatal error – all
lines and outputs are not being serviced. The fire control panel gets into the following special status:
−
Discontinuous sound signal is released - 1s sound, 3s pause, for at least an hour;
−
Only the green LED indicator is illuminated
(
Power supply
);
−
The backlight of the display is extinguished;
−
Only the power supplies are being controlled.
The fire control panel exits the status automatically 8 s after the mains supply is restored.