UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 11
Revision 7/06.12
Of 47
Table 1
Conditions of the fire control panel
Indication
All conditions -
The fire control panel is power supplied
Indicator
Power supply
–
continuous green light
Fire condition, phase Fire condition stage I
Common indicator
Fire condition
stage I
– flashing red light
Fire condition, phase Fire condition stage II
Common indicator
Fire condition
stage II
– flashing red light
Fire condition in indicated lines
Separate indicators for fire condition –
flashing red light
Pre-Fire condition in indicated lines
Separate indicators for fire condition –
continuous red light
Fire condition, phase Fire condition stage I –
inspection time has been entered
Indicator
Inspection
–continuous
green light
Fire condition and Fault condition -
sounders and outputs for fire condition has been
suppressed
Indicator
Stop Alarm
– continuous
red light
SetUp and Remote control;
Fault condition – System error
Common indicator
Fault condition
– continuous yellow light
Fault condition -
All faults except for System error and Low battery
due to interrupted mains supply
Common indicator
Fault condition
– flashing yellow light
Fault condition – System error and Circuit boards
conflict
Indicator
System error
- continuous
yellow light
Fault condition -
Fault in mains supply
Indicator
Fault in main supply -
flashing yellow light
Fault condition -
Fault in the backup batteries or in the charger
Indicator
Backup battery fault
-
flashing yellow light
Fault condition -
Fault in a controllable output
Indicator
Out of order/Disabled
controllable output –
flashing yellow light
Disabled component -
Disabled controllable output
Indicator
Out of order/Disabled
controllable output
–
continuous yellow light
Disabled component -
Disabled line or controllable output
Indicator
Disabled component
-
continuous yellow light
Test condition
Indicator
Test
–
continuous yellow light
Fire condition;
Fault – System error
Local sounder – continuous signal
Pre-Fire condition
Local sounder – discontinuous signal: 4
sound impulses for 1s, followed by 1s
break
Fault condition - All faults except for System error
and Low battery due to interrupted mains supply
Local sounder – discontinuous signal: 1s
sound 1s break
Fault condition -
Low battery due to interrupted mains supply
Local sounder – discontinuous signal: 1s
sound 3s break