UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 15
Revision 7/06.12
Of 47
The first symbol has the following meaning:
−
empty – only one line is in Fire condition;
−
“
↓
” – for the last line that entered Fire condition;
−
“
↑
” – for the first line that entered Fire condition;
−
“
” – for the rest of the lines that entered Fire condition.
For a line in Fire condition stage II the following message
appears on the display:
where N is the number of the line. In this case remaining time is not displayed. The first symbol has
the same meaning as it does in Fire condition stage I.
The messages for fire condition have a priority order. The message for the last line that has
entered fire condition is of highest priority; the message for the first line is of lowest priority. The
highest priority message suppresses all other messages. Access to all suppressed messages is
provided via keypad (see section 8.3.5). Additional information is obtained from the LED indicators.
8.3. Using the keypad
8.3.1. Button
(Inspection)
When you press the Inspection button, the time period, already programmed by the user, will be
added to the remaining time for all lines before they proceed to Fire condition stage II.
The button is active when a fire alarm line enters Fire condition stage I.
8.3.2. Button
(Stop alarm)
Press it to:
−
Switch off the local sounder for fire condition/pre-fire condition where the fire control panel has
entered Fire condition or Pre-Fore condition in a line (lines);
−
Switch off the local sounder for Fault condition upon fault condition;
−
Switch off the outputs, associated to the lines in Fire condition;
−
Illuminate the LED indicator of the button, if signalizations or outputs for Fire condition have
been switched off.
The button does not affect and is not influenced by the following events:
−
When a new line enters Fire condition or proceeds from Fire condition stage I to Fire condition
stage II, the local sounder will be activated for Fire condition/Pre-Fire condition and the
outputs associated to these lines only will be switched on;
−
When a new line enters Pre-Fire condition the local sounder will be activated for Fire
condition/Pre-Fire condition only;
−
A new Fault condition will trigger the local sounder for Fault condition only.
The LED indicator of the button stays illuminated, if the signalizations and/or the outputs remain off.
The button is active at Access level 2 (the key on the front panel is in position
).
8.3.3. Button
(Start Alarm)
It forces the proceeding to Fire condition stage II of all fire alarm lines, which have entered Fire
condition stage I, and triggers the local sounder for Fire condition/Pre-Fire condition.
At Access level 2 the action of button
can be cancelled. The signalizations are triggered
and the outputs, switched off by this button, are switched on, and the LED indicator extinguishes.
8.3.4. Button
(Reset of line)
It forces the fire control panel to exit Fire condition in the line, indicated on the LCD display, and
resets the line (cuts off the power supply for 3 seconds).
The button is active at Access level 2 (the key on the front panel is in position
).
Fire2 LnN