UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 32
Revision 7/06.12
Of 47
14.2.8. Function
Enter new password
Activate the function from the screen:
The activated function displays the following screen:
and the cursor is positioned over the first digit of 000 (password). The function enables the user to
enter a new access password for Set Up Mode.
15. Remote Control Mode
15.1. Description
The fire control panel enters Remore Control Mode when an external control unit of higher level
(computer from a centralized dispatcher control point or other) sets the panel’s configuration
parameters via serial interface. In this case the fire control panel exits all other modes/conditions.
When the fire control panel operates in Remote Control Mode, it does not serve fire alarm lines,
controllable outputs either other periphery devices (all lines and outputs are switched off); it is under
the control of the external unit. When the fire control panel exits the mode, initial reset is being done.
15.2. Indications
15.2.1. LED and sound indication
In this mode indicator
(Fault condition) illuminates in continuous yellow light, the local
sounder is switched off.
15.2.2. Text messages
The following screen is displayed:
15.3. Using the keypad
No buttons are active in this mode.
16. Saving the parameters
All set parameters or modes of operation are being saved in the energy independent memory and
upon interruption of mains or backup battery supply they remain unchanged. When the fire control
panel is powered again, it operates according the preset parameters and modes. The default
parameters and modes are factory setup (see section 14.2.6). User password is set to 000.
No telephone numbers to be dialed by the modem are entered.
17. Labour protection requirements
The installation and maintenance staff shall be well grounded in equipment’s mechanism and
operation, as well as in common technical safety regulations.
Connection to unearthed or to indirectly earthing mains supply is prohibited.
Troubleshoots are to be cleared after disconnecting the feeding cable from the mains supply.
The control panel is designed for installing in premises with a normal fire hazard, as per the Fire
Precaution Technical Regulations in Building Construction.
18. Installation and arrangements
When fire detectors and periphery devices are integrated in the system, avoid arranging wires in
closed loops; it will reduce the control panel’s resistance to electro magnetic interferences
18.1. To mount the fire control panel
-- unpack the device;
- put the dowels on the determined places;
- fasten the control panel to the dowels through the three holes provided on the chassis.
Remote Control
New Password
000
New Password