UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 12
Revision 7/06.12
Of 47
Table 2
Means of control
Condition of
the fire
control panel
Access
level
Operation
Key for access to
Level 2
Level 1
Position
Level 2
Position
Button
Reset of line
Fire condition
Level 2
To exit Fire condition in a line, indicated on
the LDC display
Button
Inspection
Fire condition
stage I
Levels 1
and 2
To add time period for inspection
Button
Stop Alarm
Fire condition
and Fault
condition*
Level 2
To suppress the local sounder and switch
off the outputs for fire condition
Button
Start Alarm
Fire condition
and Fault
condition*
Level 2
To cancel the action of
Stop Alarm
Fire condition
Levels 1
and 2
To force the transition from Fire condition
stage I to Fire condition stage II
Button
Menu
Duty mode,
Fire condition,
Pre-Fire
condition,
Fault
condition*,
Test mode and
Disabled
component
Levels 1
and 2
To enter Information and Control mode
Information
and control
Levels 1
and 2
- To enter the selected menu
- To execute the selected command
- To save a modified parameter
SetUp
Level 3А
Button
Down
Fire condition
Levels 1
and 2
To display the first or the next message for
fire condition
Information
and control
Levels 1
and 2
- To display the next element of the menu
- To move the cursor
- To modify the selected parameter
SetUp
Level 3А
Button
Up
Fault
condition*
Levels 1
and 2
To display the first or the next message for
a fault condition
Information
and control
Levels 1
and 2
- To display the previous element of the
menu
- To modify the selected parameter
SetUp
Level 3А
Button
Cancel
Disabled
component
Levels 1
and 2
To display message for disabled lines, if
any
Information
and control
Levels 1
and 2
- To exit a function without saving changes
in the parameter; the command will not be
executed
- To exit the current menu and to move to
an upper hierarchy menu
SetUp
Level 3А
* Not active in fault condition – System error and Low backup battery due to interrupted mains
supply