12. Test Mode
12.1. Description
The fire control panel enters Test Mode after a fire alarm line has been manually set to operate in
test condition. The mode can be controlled via the screens for Information and Control Mode (see
section 13.2.2).
When a fire alarm line is in test condition, the following operational changes are in effect:
−
Upon registration of Fire condition stage I or Fire condition stage II in this line the sound
indications, light indications, associated controllable and relay outputs do not operate – i.e. the
fire control panel does not enter Fire Condition;
−
Upon registration of Fault in a line the sound indicators, light indicators and the relay output for
fault condition do not operate – i.e. the fire control panel does not enter Fault Condition;
−
The events registered in the line are not saved in the energy independent memory;
−
The line is being automatically reset (the power supply is interrupted for 3 s) every 64s.
12.2. Indications
12.2.1. LED and sound indication
The common indicator
(Test) illuminates in steady yellow light. Sound signaling is not
supported.
12.2.2. Text messages
When Test Mode is not in combination with another condition,
the message
Duty
and the real time are displayed on the LCD:
The message can be suppressed from the screens for Fire Condition, Fault Condition, Disabled
Components; Disables Lines (see section 6.4).
12.3. Using the keypad
Test Mode supports 1 active button. When the fire control panel operates in combination of other
conditions, their buttons are active too.
When the message for Test Mode is displayed, the button
(Menu) is active. Press it to
enter Information and Control Mode.
13. Information and Control Mode
13.1. Description
Information and Control Mode enables the user to display information on the fire contol panel and
to enter data for control.
To enter the Information and control Mode press button
from the screens for Duty Mode,
Fire Condition, Pre-Fire Condition, Fault Condition (except for
System error
and
Low battery due to
interrupted mains supply
), Test Mode and Disabled Component; their messages will be suppressed
(see section 6.4). When the fire control panel operates in combination of other conditions, their
buttons are not active, except for button
(Stop Alarm) and button
(Start Alarm).
The Information and Control Mode does not support any specific LED or sound indication.
The screens displayed on the LCD are organized in a tree structure of subordinate menus
(Appendix 8). Transition to a menu of successive (lower) level is performed by pressing the button
; transition to a menu of previous (higher) level is performed by pressing the button
.
Moving between menus of one and the same level is performed by pressing the buttons
and
.
The screens containing particular information (information screens) or permitting parameters
change and command execution (command screens) are on the last (lowest) level.
Duty
17:05:34