UniPOS
Fire Control Panel FS5100
Instruction Manual
Page 25
Revision 7/06.12
Of 47
13.2.7.1. Menu
Boards
Select the menu from the screen
The menu contains one information screen only:
N is the type of the integrated additional module.
N can adopt the following values:
−
“NO” – without additional module
−
“1” - Module 5101;
−
“2” - Module 5102.
13.2.7.2. Menu
Line parameters
Select the menu from the screen
The menu contains 8 subordinate menus, one for each line.
Enter the menu to display the screen of the subordinate menu
for Line 1 and select the desired line.
Each subordinate menu contains information screens for the following line parameters:
−
Number of confirmation checks upon detection of level Fire
Condition:
(N is the number of the checks - 1 t
о
3)
Frequent (two or three) check ups are set for fire detectors that shall respond two or three
times before a decision for a Fire Condition is taken. In this case the time for the second and
the third check up is included in the fire detector’s response period, not in the fire control
panel’s response period.
−
Check up for a removed fire detectors:
(At N=0 no check up for a removed fire detectors is made,
а
t N=1 a check up is being made)
The check up is possible when the fire detectors are connected according the diagram in
Appendix 7a. The check up is made every 8 s, as the fire alarm line is subject to voltage 5V
and reverse polarity;
−
Period for transition from Fire condition stage I to Fire
condition stage II:
(SSS is the time period in seconds - 0 t
о
255s);
−
Current threshold above which Fire condition stage I is
detected in a line:
(CCC is the current in mA - 1 t
о
80mA);
−
Current threshold above which Fire condition stage II is
detected in a line:
(CCC is the current in mA - 1 t
о
80mA);
−
Current threshold above which Short circuit is detected in a
line:
(CCC is the current in mA - 1 t
о
80mA);
−
Current threshold below which Interruption in a line is
detected:
(CCC is the current in mA - 1 t
о
80mA);
−
Logical AND dependency of a line:
(At N=0 the current fire alarm line is not in Logical AND
dependency of another line, at N=1 t
о
8 the current fire
alarm line is in Logical AND dependency of a line having
this number (see section 6.3);
Logic &
N
Crr Intrr
CCCmA
Crr Short
CCCmA
Crr F2
CCCmA
Crr F1
CCCmA
Tm F1 – F2
SSSs
Removed FD
N
Nmbr Checks
N
Line
1
Line
Boards
N