3: Installation
3-14
UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
Figure 3.11 PowerWAVE 8000-RI DPA fuse & cable rating for single and dual feed supplies
Rack Installable UPS Frame – SINGLE FEED
Input 3x400V/230V
Bypass 3x400V/230V
Output 3x400V/230V
Battery
Fuse A
(Agl/CB)
Cable A
(mm
2
)
Max I/P
Current
Cable D
(mm
2
)
I(nom)
Fuse E
Cable E
(mm
2
)
RI-10/11/12
3x 40A
5x 6
27A
Linked to input supply
5x 6
29A
DC cables and Battery
fuses are bespoke to
the installation.
RI-20/22/24
3x 80A
5x 16
68A
5x 16
58A
RI-40
3x 160A
5x 50
136A
5x 50
116A
Fuse A
Fuse E
Load
INPUT/BYPASS FEED
Mains (3x400/230V)
Ext.
Batt.
Cable E
Cable D
Cable A
F1
F2
U
P
S
Module
1
Rectifier
Inverter
Static Switch
Static Switch
F1
F2
U
P
S Module
2
Rectifier
Inverter
UPS CABINET
Maintenance Bypass IA1
Fuse B
Fuse E
Load
INPUT FEED
Mains (3x400/230V)
Ext.
Batt.
Cable E
Cable D
Cable B
F1
F2
UPS Modul
e
1
Rectifier
Inverter
F1
F2
U
P
S Module
2
Rectifier
Inverter
UPS CABINET
Maintenance Bypass IA1
Fuse C
Cable C
BYPASS FEED
Mains (3x400/230V)
Static Switch
Static Switch
SINGLE FEED (standard)
DUAL FEED (optional)
Rack Installable UPS Frame – DUAL FEED
ALL Fuse and Cable recommendations to IEC 60950-1:2001
The fuse and cable rating details in the above tables are a recommendation only.
The UPS must be installed to prescribed IEC or local regulations (e.g. BS7671:2008)
Input 3x400V/230V
Bypass 3x400V/230V
Output 3x400V/230V
Battery
Fuse B
(Agl/CB)
Cable B
(mm
2
)
Max I/P
Current
Fuse C
(Agl/CB)
Cable C
(mm
2
)
Cable D
(mm
2
)
I(nom)
Fuse E
Cable E
(mm
2
)
RI-10/11/12
3x 40A
5x 6
27A
3x 40A
4x 6
5x 6
29A
DC cables and Battery
fuses are bespoke to
the installation.
RI-20/22/24
3x 80A
5x 16
68A
3x 80A
4x 16
5x 16
58A
RI-40
3x 160
5x 50
136A
3x 160
4x 50
5x 50
116A
Summary of Contents for PowerWAVE 8000DPA RI
Page 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Page 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...