4: Operation
4-16
UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
4.7
Replacing a UPS Module in a REDUNDANT Multi-Module System
If a UPS-module is faulty in a redundant parallel system, the load will continue to be protected by the
remaining modules which will continue to operate in the
ON-LINE
mode (
INVERTER
mode). Under these
circumstances the faulty UPS module may be replaced without having to transfer the load to bypass.
4.7.1 Extracting the UPS Module
1. Identify the faulty Module with the Alarm condition and
RESET
the Alarm. The audible noise will stop. If
the Alarm conditions persists (
ALARM
LED is red) there is a fault in the UPS-Module.
2. Verify that load is supplied by the inverter of the other modules by checking the LCD indication
LOAD
PROTECTED
.
3. On the UPS module to be replace, simultaneously press the two
ON/OFF
buttons on the UPS control
panel.
a) The LED display will give the following indications:
4. Open the fused battery isolator for the UPS module in the UPS cabinet or in the external battery cabinet/
rack, as applicable.
5. The UPS module is now totally shut-down.
6. Remove the four screws on the front of the UPS module that are fixing it to the cabinet / UPS-frame.
7. Using the two black handles, pull the UPS module forwards until the rear connectors are disconnected.
DO NOT FULLY EXTRACT THE UNIT.
8. After waiting two minutes, fully withdraw the UPS-Module from the cabinet / UPS-frame by pulling it
horizontally.
9. If you are not intending to replace the UPS module immediately, cover the UPS compartment opening
with an appropriate protection cover and secure with four screws.
WARNING:
All the operations in this section must be performed by authorised and trained
personnel.
WARNING:
A UPS module weigh up to 22kg, therefore it requires at least 2 persons to handle
the module.
Due to its weight, if the UPS module is handled inappropriately it might cause serious injury or
damage. We recommend that the modules are handled by two persons at all times.
Employ suitable lifting aids and safety platforms where possible.
WARNING:
Wait at least 2 minutes to allow the module’s electrolytic capacitors time to
discharge.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Off
BY PASS
Off
INVERTER
Off
BATTERY
Green
Summary of Contents for PowerWAVE 8000DPA RI
Page 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Page 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...