UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
4-3
4: Operation
Key function summary
ON/OFF Start-up and shutdown buttons
The UPS may be switched
ON
or
OFF
by simultaneously pressing both
ON/OFF
keys on the control panel.
This is to prevent accidental UPS start-up or shutdown.
Note:
Under normal operation, pressing the two ON/OFF simultaneously will immediately shutdown the UPS
module.
In a single module installation this will disconnect the UPS from the load.
In a parallel module system the UPS module will shutdown; however, the load may or may-not transfer to the
bypass supply in the remaining modules depending on the prevailing load and module redundancy.
To shut down all the modules in a parallel system you must press both
ON/OFF
buttons on every UPS
cabinet!
4.3
Description of the LCD display
4.3.1 Status
screens
Note:
On the right hand side of the LCD there is a 2 digit indicator defining the module’s position in a multi-
module system.The maximum number of modules in a parallel system is six.
KEYS
FUNCTION
ON/OFF
ON/OFF
Used to switch-on or switch-off the UPS.
Both keys must be pressed simultaneously.
UP
(
)
Scroll upwards through a displayed menu
DOWN (
)
Scroll downwards through a displayed menu.
RESET
Cancels the audible alarm. If the alarm condition was transient the
ALARM
LED will also extinguish, otherwise it will remain
ON
(red).
ENTER
Confirms (selects) a chosen menu item.
CAUTION: If the ON/OFF buttons are operated on all the UPS modules while the UPS is not in
Maintenance Bypass it will interrupt the load power supply.
DESCRIPTION
LCD-DISPLAY
1. Load is protected by UPS power supplied by inverter (normal
operation). The batteries are connected and OK.
LOAD
S
PROTECTED
2. Load is not protected by UPS power –supplied by mains power
(load on bypass) or it is supplied by the inverter (normal
operation) and the batteries are not OK.
LOAD
P1
NOT PROTECTED
3. Load supply interrupted. UPS has been switched off by “
ON/OFF
”
buttons.
LOAD OFF
P4
SUPPLY FAILURE
4. The UPS/module is not supplying load.
LOAD DISCONNECTED
P6
PARALLEL SWITCH OPEN
Summary of Contents for PowerWAVE 8000DPA RI
Page 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Page 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...