31
6
ASSIGNMENT OF INTERNAL FAULT 999
0-1999 internal faults generated from within System API
D1
D2
Description
10
return value of m_PwrOn_uiInitAPI()
m_PwrOn_uiInitAPI() failed
20
0
CRC32 check of ROM failed
21
0
Cyclic CRC32 check of ROM during runtime failed
22
Erroneous State
State machine for CRC32 check during runtime ran into an
invalid state
40
0
m_PwrOn_bLoadEEPROM() failed
92
Directive
ATTENTION, wrong number in the wrong module, signaled
by hchactab if control tables are not correct
200
0
Last destination element is no member of sER.sP
201
0
Last destination element is no member of sER.sM
202
0
Last destination element is no member of sER.sC
203
0
Last destination element is no member of sER.sH
204
0
Destination is no member of sER.sX
210
sEECtrl.sChk.uiReadStartAddr
Refresh cycle timeout expired
211
sEECtrl.sChk.uiReadStartAddr
Uncorrectable error in EEPROM block
212
sEECtrl.eSeq_State
Invalid state
215
uiEEFaultAddr
Uncorrectable error in Parameter Set
216
uiEEFaultAddr
Uncorrectable error in Miscell-Data
217
uiEEFaultAddr
Uncorrectable error in Curve Set
220
0
pucDst == NULL
222
uiEEStartAddr
Invalid EEPROM address
240
uiEEStartAddr
Write beyond end of safety area!
241
uiEEStartAddr
Start address in safety area is no multiple of 3
242
uiEEStartAddr
Write beyond end of non-safety area!
243
uiEEStartAddr
Start address is in reserved area!
244
ulReqFIFOSpace
Not enough FIFO space
250
(ulong32)pucDst
Readback error while refreshing - possibly defective RAM cell
300
0
Timout sICom.uiRxLiveTimer expired
301
0
Timout sICom.uiRxLiveTimer expired
350
0
Timeout sICom.uixLiveTimer expired
360
0
Timeout while waiting for the exit from
DUAL_BEF_CHECK_PARAM
361
0
FIFO ful !
380
uiBPP_HPPunktNr
Error while calling uiPutPunkt()
381
0
Seal control command in the presence of
BM_FAT_KALTCHECK
382
0
Timeout in the cyclical parameter comparison
383
uiBCP_AnzParam[0]
DUAL_BEF_CHANGE_PARAM1: Invalid value in the
reception buffer
384
uiBCP_AnzParam[1]
DUAL_BEF_CHANGE_PARAM2: Invalid value in the
reception buffer
385
sRx.Buffer.ui[ucRxOK-1][uiSTART-
BEF+47]
Cyclic parameter verification: different parameters between
HP and UP!
386
uiParaIdx
PowerOn parameter verification: different parameters
between HP and UP!
410
sIO.sIn.ulInputsN
Detected positive half-wave on terminal input!
411
input status received from UP
Different input status between controllers
412
0
The readback input of the fuel selection relais contacts in
the dual fuel is invalid. DFM probably defect.
420
uil
Input status of digital input on HP and UP is inconsistent
(>20ms)
430
ucPin2Test
Pin short circuit test detected an error!Currently tested pin
not configurated as output or is stuck at 1
Summary of Contents for LAMTEC BT3 Series
Page 46: ...PART IV MAINTENANCE 46...
Page 47: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 114: ......
Page 123: ......
Page 124: ......
Page 125: ...WB1 QF A QF B...
Page 126: ......
Page 127: ......
Page 129: ......
Page 130: ......
Page 131: ...INTERFACE...
Page 132: ...R1 R2 POT...
Page 135: ......
Page 136: ......
Page 137: ......