PART III: OPERATION
34
Click up to quit the ignition position.
Check the combustion quality in all positions (from mini-
mum to maximum output) and adjust the gas and air
setting if necessary (as indicated on chapter “SETTING
THE IGNITION POINT WITH BURNER IN
STAND?BY”).
Set the maximum load position 999, according to the
maximum output required by the boiler. If necessary,
set the inlet gas pressure (at the exit of the gas pres-
sure reducer). Check the output combustible and the
quality of combustion in all positions and adjust gas and
air if necessary (see chapter “SETTING THE IGNITION
POINT WITH BURNER IN STAND?BY”).
Press EXIT to quit the combustion settings.
Press ENTER to save the new settings.