16
3.2
MANUAL MENU PATH
From previous page (see chapter 3) use the cursor keys
to select
and confirm this with
Enter
1
Pictogram Manual
2
Start burner manually [off]
3
Adjust burner manual output
4
Pictogram confirm settings
The "Burner ON" control loop does not need to be switched on to start the burner from this menu. The user interface
assumes control in this menu. If there is no contact with "Burner ON" signal from other sources (terminal X10.2), the
software switches off the burner when you exit the menu.
If the burner is switched on manually via display, the BT300 no longer responds to the "Burner ON" signal input at
connector X10.2. It is for this reason that limiters, monitors and other similar safety functions must not be used with
this input!
Leaving the window terminates burner operation!
3.2.1 REGOLAZIONE MANUALE % CARICO BRUCIATORE
Use the cursor keys
to select the adjustment of the burner firing‐rate in % and confirm this selection
with Enter
Please note, that you can adjust the burner firing‐rate only while burner is running. Start the burner before you
adjust the burner firing‐rate as mentioned above.