52
Holding
Register
Type
Value
Comments
40010
Read / Write Contact
Reception
Notification
0 = Off
1 = Show Contact Reception on LCD
SMART 3000 LCD will flash Contact Reception
on LCD and sound chime. User may accept
alert by touching any button on SMART 3000
40011
Read Only
Room
Temperature
Value / 10 (e.g. 21.7C = 217)
40012
Read / Write Temperature
Display
0 = Show Room and Set Temperature
1 = Show Set Temperature Only
40013
Read / Write Native F/C
Display
1 = Degree F format
0 = Degree C format
40014
Read / Write User Setpoint
High Limit
Range 41 to 86°F (5 to 30°C) in 1°F/C Steps
1:1
40015
Read / Write User Setpoint
Low Limit
41 to 86°F Range (5 to 30°C) in 1°F/C Steps
1:1
40016
Read / Write Deadband
1.0 to 10.0°F degrees in 1°F degrees Steps
0.5 to 5.0°C degrees in 0.5°C degrees Steps
Value / 10 (e.g. 1.5°C Deadband = 15)