50
Holding
Register
Type
Value
Comments
40001
Read Only
Device ID
Always Returns 131
Use As A Sentinel Point
40002
Read Only
Firmware
Version
Divide By 100 (e.g. Version 2.36 = 236)
40003
Read Only
DIP Switch
State
Binary Count
Sw1 = 1, Sw2 = 2, Sw3 = 4, Sw4 = 8 etc
40004
Read / Write Occupancy
Status
0 = Room is Unoccupied
1 = Room is Occupied
Note - ModBus can write 0 holding the room
unoccupied regardless of the occupancy input.
Modbus cannot override the occupancy input
and hold the SMART 3000 in occupied mode.
40005
Read Only
Bell Status
0 = Bell Is Silent
1 = Bell Is Chiming
40006
Read / Write Door Station
Status
0 = Normal - No Activity
1 = Make Up Room Active
2 = Do Not Disturb Active