31
The SMART 3000 will automatically restart once the window is closed.
The Installer Menu option 31 Window Input Logic and option 32 Window Input
Delay sets the window detection logic in the SMART 3000.
Door Switch
The Door switch input (DS) is used by the SMART 3000 for two functions.
1. To detect that the door has been opened and then closed to let somebody
into or out of the room.
2. To detect if the door has been left open.
The door switch input can be set for a Normally Open (switch open when door
is closed) or Normally Closed logic (switch closed when door is closed). Installer
Menu option 33 Door Input Logic and option 34 Door Input Delay sets the door
detection logic in the SMART 3000.
Entering or exiting the room.
Once the door is opened and then closed
the SMART 3000 will begin its occupancy detection process using the PIR input
described below. Based on the outcome of this process the SMART 3000 will
remain ON and permit guest interaction with the SMART 3000 (adjust mode and
setpoint for example), or switch to Unoccupied mode where the SMART 3000
will substitute the guest setpoint and mode for the installer pre-set values.