11
DIP Switches
Table 1
DIP Switch Settings
Switch
Function
On
Off
Sw1
Indoor Fan Mode
3 Fan Speed
1 Fan Speed
Sw2
Equipment Type
Heat Pump
Heat Cool
Sw3
HP Mode (Sw2= ON)
HC Mode (Sw2=OFF)
Rev Valve Heat (B)
HE – Fan With
Heat Thermostat
Controlled
Rev Valve Cool (O)
HG – Heater Fan
control by Heater
Sw4
2 / 4 pipe mode
2 Pipe Mode
4 Pipe Mode
Sw5
Comp Protection
Delay
5 Min Anti Cycle
Immediate
Compressor Start
Sw6
Not Used
Sw7
Ventilation Mode
Permitted
Not Permitted
Sw8
Door Station
(Optional)
Fitted
Door Station Not
Used
Summary of Contents for SmartSense SMART 3000