MOUNTING INSTRUCTIONS

TC500A-N Commercial Thermostat 

CONNECTED DEVICE FOR COMMERCIAL BUILDINGS

 

SUPPORTED DOCUMENTS

• TC500A-N Commercial Thermostat Datasheet (31-00398M)

• TC500A-N Commercial Thermostat User guide (31-00400M)

• TC500A-N Commercial Thermostat Quick start guide (31-00401M)

                                                            

                                                          31-00399M-01 | Rev.10-20

E

Keep these instructions together with the 

device or with the equipment 

documentation! Only qualified personnel 

may perform electrical connections for 230 

VAC.

F

Cette instruction est à conserver avec le 

contrôleur ou avec la documentation de 

l'installation ! Le raccordement électrique 

pour le 230 VAC ne peut être effectué 

que par le personnel autorisé.

P

Guarde estas instruςões junto do regulador 

ou junto da documentaςão da instalaςão! A 

ligaςão eléctrica a 230 VAC só deve ser 

efectuada por pessoal especializado.

D

Diese Anleitung ist beim Gerät oder in der 

Anlagendokumentation aufzubewahren! 

Elektrisches Anschließen von 230 VAC ist 

nur durch autorisiertes Fachpersonal 

gestattet.

I

Queste istruzioni devono essere 

conservate insieme al lettore o con la 

documentazione dell´impianto! I 

collegamenti a 230VCA devono essere 

eseguiti da personale qualificato.

S

Denna instruktion skall förvaras tillsammans 

med regler eller 

anläggningsdokumentationen! Elektrisk 

anslutning med 230 VAC får endast utföras 

av behörig personal.

DK

Opbevar denne vejledning sammen med 

regler eller med anlægsdokumentationen! 

Elektrisk tilslutning for 230 VAC bør kun 

foretages af autoriserede personer.

N

Denne veiledningen skal oppbevares 

sammen med regler eller 

anleggsdokumentasjonen! Elektrisk 

tilkopling med 230 VAC må kun utføres 

av fagfolk.

FI

Tätä ohjetta tulee säilyttää laitteen 

läheisyydessä tai yhdessä muiden 

dokumenttien kanssa! Vain asianmukaiset 

oikeudet omaava henkilö saa suorittaa 230 

VAC käyttöjännitteen liitäntätöitä.

ES

Conserve estas instrucciones con el recalar 

o con la documentación de la instalación. 

La conexión eléctrica a 230 VCA debe 

hacerse solamente por personal 

qualificado.

NL

Deze handleiding moet bij de regelaar, of 

met de documentatie van de installatie 

worden bewaard! De elektrische 

aansluiting voor 230 VAC mag alleen door 

geautoriseerd personeel worden 

uitgevoerd.

PL

Instrukcję obsługi należy przechowywać 

przy urządzeniu albo w dokumentacji 

technicznej. Tylko autoryzowany servis jest 

upoważniony do podłączenia do 230 VAT.

SC

请将此装配说明书与设备或者与设备的其
他文档保存在一起! 230 V 交流电的接线
操作仅允许由合格的专业人员执行

TC

請將此裝配說明書與設備或者與設備的
其他文件儲存在一起!
僅能由合格的專業人員進行230 V交流

電的接線作業。

K

본 설치 설명서를 해당 장치 또는 관련
문서와 함께 보관하시기 바랍니다

.

230VAC 

전원 연결은 관련 작업 전문가에

의해 수행되어야 합니다

.

Summary of Contents for TC500A-N

Page 1: ...a instruktion skall förvaras tillsammans med regler eller anläggningsdokumentationen Elektrisk anslutning med 230 VAC får endast utföras av behörig personal DK Opbevar denne vejledning sammen med regler eller med anlægsdokumentationen Elektrisk tilslutning for 230 VAC bør kun foretages af autoriserede personer N Denne veiledningen skal oppbevares sammen med regler eller anleggsdokumentasjonen Elek...

Page 2: ...ntrol If you have questions contact Honeywell Customer Care Center Location Do not install the Thermostat unit where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat IMPORTANT To avoid electrical interference which c...

Page 3: ...1 Y2 Y3 are powered from the Thermostat s transformer Minimum load includes Thermostat and analog outputs at full load Max 10V voltage output with 2Kohms load Every relay output is N O Normally Open contacts with a maximum switch rating of 24VAC 1A 24VA The allowed maximum load is 96VA which assumes all 8 relay output loads are powered from the controller transformer Actual power requirements depe...

Page 4: ... with the wall 5 Pull the wires through the wiring opening of the wall plate and position the wallplate over the mounting holes 6 Insert the screws into the holes and tighten screw torque 0 1Nm Mounting the wallplate on the gang box optional The thermostat wallplate can be mounted vertically on a US 2 4 or UK 75 75mm gang box which is already installed onto the wall and wired 1 Before mounting the...

Page 5: ...UI1 1 Universal input COM Common UI2 2 Universal input COM Common Sylk Sylk bus master power output Sylk bus master power output RS485 BACnet Communications _ BACnet Communications R RC Jumper between R and RC for single transformer system remove the jumper in two transformer system 24VAC RC 24VAC power from cooling Class 2 transformer G Fan Y1 Relay output Compressor contactor stage1 Y2 Relay out...

Page 6: ...rt stranded wire end into the wiring terminal push the Release tool into the Tool hole and insert the wires Fig 7 Wire release 4 Push excess wire back into the hole 5 Check for loose or frayed wire that may cause a short Mounting the display unit After all wiring activities have been performed install the display unit onto the wallplate 1 Hold the display unit in a tilted position so that the latc...

Page 7: ...TC500A N TC500A W COMMERCIAL THERMOSTAT 7 31 00399M 01 Rev 10 20 DIMENSIONS 3 19 32 91 2 mm 4 15 32 113 7 mm 4 x 11 32 9mm 2 3 8 60 3mm 3 1 4 82 75mm 4 x 3 16 4 5mm ...

Page 8: ...AL THERMOSTAT U S Registered Trademark 2020 Honeywell International Inc 31 00399M 01 Rev 10 20 Honeywell Building Solutions Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com ...