background image

TC500A-N/TC500A-W COMMERCIAL THERMOSTAT

31-00399M-01 | Rev.10-20

4

Mounting wallplate on the dry wall

The thermostat wallplate can be mounted vertically on the 

wall. It supports 18-22 AWG (0.5-0.75mm2) wires.

1.

Before mounting the wallplate, make sure that the 

wire ends (not cables) are stripped for the length 

marked on the wallplate.

Fig. 4. Wire strip length

2.

Position and level the wallplate along the wall and 

mark the drilling location using a pencil. 

Fig. 5. Wallplate drilling locations

3.

Remove the wallplate and drill two pilot holes on the 

wall, on the marks. For drywall, drill 3/16-in. holes. 

For firmer material such as plaster, drill 7/32-in. 

holes. 

4.

Gently tap anchors (provided in kit) into the pilot 

holes until flush with the wall.

5.

Pull the wires through the wiring opening of the wall

-

plate and position the wallplate over the mounting 

holes.

6.

Insert the screws into the holes and tighten (screw 

torque 0.1Nm).

Mounting the wallplate on the gang 

box (optional)

The thermostat wallplate can be mounted vertically on a 

US 2”*4” or UK 75*75mm gang box which is already 

installed onto the wall and wired.

1.

Before mounting the wallplate, make sure that the 

wire ends (not cables) are stripped for the length 

marked on the wallplate.

2.

Pull the wires through the wiring opening of the wall

-

plate, and position the wallplate along the gang box 

to align the mounting holes. For gang box screw 

holes, refer to Fig. 5.

3.

Insert the screws into the holes and tighten.

4 x 11/32”
(9mm)

2 - 3/8” 

(60.3mm)

(UK 75X75cm

gang box

screw holes)

4 x 3/16”  
(4.5mm)

Drilling location for

wall mounting

Drilling location for wall mounting

3 - 1/4” 

(82.75mm)

(US 2”X4” gang box

screw holes)

Summary of Contents for TC500A-N

Page 1: ...a instruktion skall förvaras tillsammans med regler eller anläggningsdokumentationen Elektrisk anslutning med 230 VAC får endast utföras av behörig personal DK Opbevar denne vejledning sammen med regler eller med anlægsdokumentationen Elektrisk tilslutning for 230 VAC bør kun foretages af autoriserede personer N Denne veiledningen skal oppbevares sammen med regler eller anleggsdokumentasjonen Elek...

Page 2: ...ntrol If you have questions contact Honeywell Customer Care Center Location Do not install the Thermostat unit where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat IMPORTANT To avoid electrical interference which c...

Page 3: ...1 Y2 Y3 are powered from the Thermostat s transformer Minimum load includes Thermostat and analog outputs at full load Max 10V voltage output with 2Kohms load Every relay output is N O Normally Open contacts with a maximum switch rating of 24VAC 1A 24VA The allowed maximum load is 96VA which assumes all 8 relay output loads are powered from the controller transformer Actual power requirements depe...

Page 4: ... with the wall 5 Pull the wires through the wiring opening of the wall plate and position the wallplate over the mounting holes 6 Insert the screws into the holes and tighten screw torque 0 1Nm Mounting the wallplate on the gang box optional The thermostat wallplate can be mounted vertically on a US 2 4 or UK 75 75mm gang box which is already installed onto the wall and wired 1 Before mounting the...

Page 5: ...UI1 1 Universal input COM Common UI2 2 Universal input COM Common Sylk Sylk bus master power output Sylk bus master power output RS485 BACnet Communications _ BACnet Communications R RC Jumper between R and RC for single transformer system remove the jumper in two transformer system 24VAC RC 24VAC power from cooling Class 2 transformer G Fan Y1 Relay output Compressor contactor stage1 Y2 Relay out...

Page 6: ...rt stranded wire end into the wiring terminal push the Release tool into the Tool hole and insert the wires Fig 7 Wire release 4 Push excess wire back into the hole 5 Check for loose or frayed wire that may cause a short Mounting the display unit After all wiring activities have been performed install the display unit onto the wallplate 1 Hold the display unit in a tilted position so that the latc...

Page 7: ...TC500A N TC500A W COMMERCIAL THERMOSTAT 7 31 00399M 01 Rev 10 20 DIMENSIONS 3 19 32 91 2 mm 4 15 32 113 7 mm 4 x 11 32 9mm 2 3 8 60 3mm 3 1 4 82 75mm 4 x 3 16 4 5mm ...

Page 8: ...AL THERMOSTAT U S Registered Trademark 2020 Honeywell International Inc 31 00399M 01 Rev 10 20 Honeywell Building Solutions Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com ...

Reviews: