32
Door Left Open.
When the door is left open for longer than the pre-set time
(0 to 300 seconds) the SMART 3000 will automatically turn OFF. The text OFF
will flash in the display to indicate that the remote door (or window switch) is
holding the SMART 3000 in OFF mode.
The SMART 3000 will automatically restart once the door is closed.
PIR input
A PIR (passive infra-red) movement detector can be directly wired to the SMART
3000 PIR input. As movement is detected by the PIR it will send multiple On/Off
pulses to the SMART 3000 every time it detects movement. The SMART 3000
using this data along with door switch data will determine the occupancy status
of the room and behave accordingly.
NOTE:
The PIR must be powered separately, typically from a 12V DC supply.
Automatic Occupancy Detection Logic
Automatic occupancy detection requires the door switch and PIR input to be
wired and working.
When the door is first opened the SMART 3000 instantly enters Occupied mode
where the SMART 3000 will permit the guest to set their desired temperature
and mode of operation. Once the door is closed, the SMART 3000 will sense
movement as detected by the PIR sensor wired to the PIR input. If no movement
is seen in the installer pre-set seek time (installer adjustable 1 to 15 minutes)
Summary of Contents for SmartSense SMART 3000
Page 19: ...19 Figure 6 Figure 7...