59
Holding
Register
Type
Value
Comments
40051
Read / Write 0 to 10 Fan
Minimum
Voltage
0 to 10V (Fan value x 10)
40052
Read / Write 0 to 10 Heat
Interval
10 to 300 seconds in 10 second steps
(60 seconds default)
40053
Read / Write 0 to 10 Heat
Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40054
Read / Write 0 to 10 Heat
Minimum
Voltage
0 to 10V (Heat value x 10)
40055
Read / Write 0 to 10 Cool
Interval
10 to 300 seconds in 10 second steps
(60 seconds default)
40056
Read / Write 0 to 10 Cool
Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40057
Read / Write 0 to 10 Cool
Minimum
Voltage
0 to 10V (Cool value x 10)
40058
Read / Write Window input
logic
0: Normally Open
1: Normally Closed