58
Holding
Register
Type
Value
Comments
40045
Read / Write Buttons
shown on
display
0: Both mode and fan buttons show (default)
1: Show mode but hide fan button
2: Show fan but hide mode button
3: Hide both mode and fan buttons
40046
Read / Write Permitted
Modes
0: Off / Auto
1: Off / Heat / Cool / Auto
2: Off / Heat / Cool
3: Off / Heat
4: Off / Cool
40047
Read / Write Swap F/C
display shown
on display
1: F/C button shown
0: F/C Button hidden
40048
Read / Write Fan Span for 3
speed relays
1.0 to 6.0°F degrees/0.5 to 3.0°C degrees in
1°F degree/0.5°C degrees steps
Data format : Fan span * 10
40049
Read / Write 0 to 10 Fan
Interval
10 to 300 seconds in 10 second steps (60
seconds default.
40050
Read / Write 0 to 10 Fan
Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)